NA2XY-O or -J

Underground cable with XLPE insulation and PVC sheath

Underground cable with XLPE insulation and PVC sheath

Standard: DIN VDE 0276-603 (HD 603)
Design
1 Aluminium conductor, round solid (RE), sector-shaped solid (SE), round stranded (RM), resp. sector-shaped (SM)
2 Core insulation (XLPE)
3 Inner covering (EPDM)
4 Sheath (PVC black, UV-resistant)
Application
Power distribution cables in power stations, industrial installation and switchgears, as well as in local mains.
For fixed installation underground, in interior premises, cable ducts, in the open air and in water – as permitted by the local building regulations – if no risk of any mechanical damage is to be expected.

Technical Data
Rated voltage: kV 0,6/1
Test voltage: kVeff 4.000
Laying temperature: °C min. -5
Operating temperature: °C -50 up to +90
Conductor temperature: °C max. +90
Short-circuit temperature: °C/s max. +250/5
Core identifikation:   HD 308 S2 (VDE 0293)
Bending radius (mind.) mm 12 × Ø of cable
Certificate:   VDE, EZU Tschechien
Flame retardant:   acc. to EN 60332- 1-2

NA2XY-O or -J

Underground cable with XLPE insulation and PVC sheath

no. of cores
x nom. cross
section
max.
conductor
resistance
current
rating
in the ground
current
rating
in the air 1)
outer
diameter
AL-
number
total
weight
 
mm²

Ohm/km

A

A
appr.
mm
appr.
kg/km
appr.
kg/km
200648 NA2XY 1 × 25 RE 1.200 177 136 11,5 73 191
200649 NA2XY 1 × 35 RE 0.868 212 166 12,5 102 231
200574 NA2XY 1 × 50 RM 0.641 252 205 14,5 145 292
200650 NA2XY 1 × 70 RM 0.443 310 260 16,3 203 390
200651 NA2XY 1 × 95 RM 0.320 372 321 18,1 276 480
200652 NA2XY 1 × 120 RM 0.253 425 376 19,8 348 556
200494 NA2XY 1 × 150 RM 0.206 476 431 21,5 435 675
200495 NA2XY 1 × 185 RM 0.164 541 501 23,8 537 830
200496 NA2XY 1 × 240 RM 0.125 631 600 26,3 696 1.059
200481 NA2XY 1 × 300 RM 0.100 716 696 29,0 870 1.260
200575 NA2XY 1 × 400 RM 0.078 825 821 31,8 1.160 1.560
200653 NA2XY 1 × 500 RM 0.061 952 971 36,5 1.450 1.949
200576 NA2XY 1 x 630 RM* 0.047 1.102 1.151 41,9 1.827 2.386

* conductor is not compressed

→ Other cross-sections on request.

1) Basic rated current acc. to DIN VDE 276-603 (HD 603)

Technical values can change. No responsibility is therefore taken for correctness.