NY2Y-J

Underground cable with PVC insulation and HDPE sheath

Underground cable with PVC insulation and HDPE shealth
Standard: DIN VDE 0276-603
Design
1 Copper conductor, round solid (RE), round stranded (RM), resp. sector-shaped (SM)
2 Core insulation (PVC)
3 Inner covering (EPDM)
4 Sheath (HDPE black, UV-resistant)
Application
Power distribution cables in power stations, industrial installation and switchgears, as well as in local mains.
For fixed installation underground, in interior premises, cable ducts, in the open air and in water – as permitted by the local building regulations – under severe mechanical stressing during installation and operation.
Technical Data
Rated voltage: kV   0.6/1
Test voltage: kV/Hz     4/50
Laying temperature: °C     min. -5
Operating temperature: °C     -50 up to +70
Conductor temperature: °C     max. +70
Short-circuit temperature: °C/s     max. +160 /5
Core identifikation:       HD 308 52
Bending radius (mind.) mm     12x Ø of cable

NY2Y-J

Underground cable with PVC insulation and HDPE sheath

no. of cores
x nom. cross
section
max.
conductor
resistance
current
rating
in the ground
current
rating
in the air
outer
diameter
Cu-
number
total
weight

mm²

Ohm/km

A

A
appr.
mm

kg/km

kg/km
200341 4 x 10 RE 1,830 79 59 19,0 384 740
200342 5 x 10 RE 1,830 79 59 20,6 480 884
200393 4 x 16 RE 1,150 102 79 23,0 614 1.054
200394 5 x 16 RE 1,150 102 79 24,5 768 1.227
200343 4 × 25 RM 0,727 133 106 26,7 960 1.475
200344 5 × 25 RM 0,727 133 106 29,9 1.200 1.825
200345 4 × 35 RM 0,524 159 129 29,6 1.344 1.910
200346 4 × 50 SM 0,387 188 157 34,4 1.920 2.322
200347 4 × 70 SM 0,268 232 199 43,0 2.688 3.125
200348 4 × 95 SM 0,193 280 246 46,6 3.648 4.319
200350 4 × 120 SM 0,153 318 285 46,6 4.608 5.290
200351 4 × 150 SM 0,124 359 326 50,4 5.760 6.381
200352 4 × 185 SM 0,099 406 374 57,0 7.104 8.137
200353 4 × 240 SM 0,075 473 445 63,2 9.216 10.589

→ Other cross-sections on request.

Technical values can change. No responsibility is therefore taken for correctness.