Steel ropes

galvanised

DIN 48201/3
The calculated breaking force is acc. to DIN 48203/3.
nominal section actual section no. of wires wire diameter conductor diameter calc. breaking force weight
  mm² mm²   mm mm kN kg/km

St I
400501 25 24,25 7 2,10 6,3 8,98 192
400502 35 34,36 7 2,50 7,5 12,73 272
400503 50 49,48 7 3,00 9,0 18,33 391
400504 50 48,35 19 1,80 9,0 17,91 384
400505 70 65,81 19 2,10 10,5 24,38 523
400506 95 93,27 19 2,50 12,5 34,56 741
400507 120 116,99 19 2,80 14,0 43,34 929

St II
             
400511 25 24,25 7 2,10 6,3 15,90 192
400512 35 34,36 7 2,50 7,5 22,52 272
400513 50 49,48 7 3,00 9,0 32,43 391
400514 50 48,35 19 1,80 9,0 31,69 384
400515 70 65,81 19 2,10 10,5 43,14 523
400516 95 93,27 19 2,50 12,5 61,14 741
400517 120 116,99 19 2,80 14,0 76,69 929

St III
             
400521 25 24,25 7 2,10 6,3 30,18 192
400522 35 34,36 7 2,50 7,5 42,76 272
400523 50 49,48 7 3,00 9,0 61,58 391
400524 50 48,35 19 1,80 9,0 60,17 384
400525 70 65,81 19 2,10 10,5 81,00 523
400526 95 93,27 19 2,50 12,5 116,07 741
400527 120 116,99 19 2,80 14,0 145,59 929

→ Other cross-sections on request.

Technical values can change. No responsibility is therefore taken for correctness.